Document LTP0099 rev 2a
Adjusting Water Flow Using ΔT (Delta-T)
The Delta-T is the temperature difference between the water temperatures entering and leaving the chiller. The equipment can be fine-tuned for maximum performance by balancing water flow rates to maintain an ideal ∆T.
- Installed Temperature / Pressure probes and ports are required to perform the following procedures.
- This adjustment procedure is to be completed with the unit in HEA mode only; ACH and COO discharge temperatures are not shown.
Please Note -
Temperature / Pressure ports are required for all commercial applications.
They are strongly recommended (but not required) for residential installations.
- Adjust chiller's thermostat to its lowest setting while in HEA mode.
- Deactivate the water filtration pump.
- Adjust the valves controlling water headed towards the chiller to the half open position.
- Adjust the valves controlling water leading away from the chiller to a fully open position..
- Activate the pool water filtration pump.
- Slowly raise the thermostat temperature until the chiller activates.
- After a four-minute delay, the chiller's compressor will start.
- With the chiller running, confirm water filtration pump is operating properly with adequate flow and no short cycling. Confirm that the filters leading to the chiller are clean.
- Wait for water and refrigerant pressure to stabilize (approximately 5 minutes).
- Adjust valves in the following order:
- Adjust the valve that controls water exiting the chiller. Match the temperature measured with a temperature pressure probe to the chart. See "Temperature Chart"
- Allow pressure to stabilize. Then check temperature again. Re-adjust the valve controlling the water exiting the chiller as needed.
- Mark valves at these positions for future reference.
Temperature differences are based on pool temperatures of 72° (+ or – 3° F). For water temperatures outside this range, contact AquaCal® Technical Support.
| MODEL |
|
|---|---|
| TC500 | 2° to 5° F |
| TC1000 | 2° to 5° F |