Three-Phase Adjustment
DANGER
Failure to heed the following will result in injury or death.
- Deactivate power while routing wiring to control board.
- Follow all National Electric Codes (NEC) and/or State and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
- The information contained in this section is intended for use by qualified technicians, familiar with electrical service-industry safety standards and methods.
NOTICE
Failure to heed the following may result in damage to equipment.
- Setting a voltage other than what is listed on the heat pump’s data plate can damage equipment and is not covered under warranty.
If a three-phase unit fails to operate at start-up, the orientation of the line voltage "field" wiring may need to be adjusted.
- Units equipped with the ICM Digital Three-Phase Monitor will display a "Back Phase Rev" fault code on the phase monitor display.
- The phase monitor is located inside the electrical panel.
- Deactivate power to the unit. Confirm that power is off to all three legs using an electrical test meter set for the correct voltage.
- Switch position of the incoming power wires at each leg as follows, re-connect power and attempt to restart the unit. If the unit fails to start, disconnect power. Verify off and proceed to the next leg.
- Switch incoming power wires at L1 and L2 on the line side to the contactor.
- Switch incoming power wires at L1 and L3 on the line side to the contactor.
- Switch incoming power wires at L2 and L3 on the line side to the contactor.
- When heat pump starts, disconnect power and verify off. Then confirm all line voltage connections are securely tightened. Reconnect power.
- If the heat pump does not start, contact AquaCal® for further assistance.